1982, 07-08 Fire Hydrants3POF2\N1I V7LL1(I FIRE DEPARTMENT --�
s4 e D€ 4 /
EAST 10319 SPRAGUE AVE. • SPOKANE, WASHINGTON 99206 • TELEPHONE (509) 928-1700
,7a4 , //axe, exeea4i,e ,auefaz
July 8, 1982
Spokane County Department Building Code
N811 Jefferson
Spokane, Washington 99260
Complex: Feldman & Person 4 plexes
S1500 Bluff Dr. 6-4 plexes
Building Permit #82A-5207,5209,5212,5214,5216
5218, Bluff Dr. S.1520, 1414
1426-1512-1504-1506
The required fire flow for this complex is
2250 GPM. This complex requires 2 fire hydrants
to be installed. The hydrants shall be installed
as per approved water plan and shall be installed
prior to construction of complex. Each hydrant
shall be capable of flowing a minimum of 1500
GPM at 20 PSI residual when any 2 hydrants are
flowing simultaneously. The bottom of the lowest
outlet of the hydrant shall be no less than 18
inches above finished grade.
Credit is given for 1 existing hydrant located
on Lot #4. One new fire hydrant shall be installed
on the west side of Bluff Drive, 130 ft. south
of the north lot line of Lot 1.
The access roadways to 2 of the buildings need
to be widened to UFC 79ed, Ch. 10.207(a) requirements
and or meet Fire Department approval.
ncere
DR:sn
oug er
Fire ief
C.C. Grant Person
Jim Fuller, Washington Water Power
PRE VENT FIRES - SAVE LIVES f