2005, 01-18 InspectHouse moving inspection report for 12324 E. Maxwell. 1-18-05
The following items were noted during a walk through inspection at the above
address. These items shall be incorporated into the relocation of the home once it
is reset on a new basement foundation.
1. One egress window is required in each bedroom and one in the unfinished
basement that meets all of the following:
Maximum sill height of 44", minimum openable area of 5.7 sq. ft., minimum
openable width of 20", and a minimum openable height of 24".
2. Wired in smoke detectors will be required on each level of the house and in
each bedroom.
3. Exhaust fans rated at least 50cfm will be required in each bathroom and
laundry room. The kitchen area will require an exhaust fan rated at 100cfm.
All fans shall be vented to the exterior.
4. After the home is set on the foundation, all of the water piping and drainage
piping must be tested of leaks.
5. The attic must be insulated to R-38.
6. All exterior walls shall be insulated to their full capacity.
7. All windows that are replaced shall have a U -value of .35 or better.
8. Maintain all existing bearing points of the floor system.
9. The new basement must meet current code requirements for insulation, egress,
and radon requirements.
10. Additional permits will be required for the mechanical system installed in the
basement.
11. A fire wall between the house and attached garage will be required using at
least 'A" drywall.
12. After reviewing the new foundation plan, it appears that new square footage is
being added to the home of approximately 10'x55'. Please clarify this.
Sincerely: t,
Kevin ///
Building Inspector