2001, 07-25 Dept of Health Plan Review Comments: New Boiler Plant RECEIVED
• SPOKANE COUNTY
Letter of Transmittal J U L 3 0 2001 A Washington State Department of
July 25, 2001 ' t. 1' Q AND CODE ENFORCEMENT eaHit
BY:
Construction Review Services
2725 Harrison Ave.NW Suite 500
PO Box 47852
Olympia,Washington 98504-7852
TOM FOX
VALLEY HOSPITAL & MEDICAL CENTER
12606 EAST MISSION
SPOKANE WA 99216
Project Info:
CRS#6153 Project 12606 EAST MISSION AVE.
VALLEY HOSPITAL location: Spokane,WA 99216
Chapter 246-320 WAC Hospitals
New boiler plant
Key People:
Administrator: Michael Liepmann Facility Tom Fox
12606 East Mission Ave Contact: 12606 East Mission
Spokane,WA 99216 Spokane,WA 99216
(509)922-9462 (509)922-9469
Email Email
Architect/ Nortwest Architectural
Engineer: Benson Nielson
1203 W Riverside Ave
Spokane,WA 99201
(509)838-8240
Email
Reviewers:
Architect: Richard M.Swanson Fire&Life Chad E.Beebe,CSI
richard.swanson@doh.wa.gov Safety: chad.beebe@doh.wa.gov
(360)705-6782 (360)705-6648
Rob Bradley
rob.bradley@doh.wa.gov
(360)705-6784
Sanitarian: John R.Templar Mech./ William M. Kingrey,PE
john.templar@doh.wa.gov Electrical: william.kingrey@doh.wa.gov
(360)705-6786 (360)705-6783
Copies To:
® Local Building Official:Spokane County 0 Washington State Patrol,Fire Protection Bureau
❑ DOH Office of Accommodations&Res.Care Survey 0 DSHS,Jill Brady,Boarding Home Licensing Program
❑ DOH Child Birth Center Licensing 0 DSHS,Residential Care Services,
❑ DOH Office of Health Care Survey ❑ Other:
❑ Architect/Engineer:Nortwest Architectural ® CRS File
❑ Contractor:
Page 1 of 3 Plan Review Comments for Project#6153
•
VALLEY HOSPITAL
Chapter 246-320 WAC Hospitals
New boiler plant
•
Memo:
• This project is not approved and is not yet authorized for use by the Licensing Agency.
• Please provide written responses to our review,using our numbering system, for those items checked
as not approved,
• Include two copies of revised plans or sheets, in the same format/size as the original submission,
incorporating your corrections.
• Any response that does not address ALL the review comments and provide the required information
will be considered incomplete and returned without review.
• The project sponsor should review with the consultants what is being submitted in all submissions.
•
Page 2 of 3 Plan Review Comments for Project#6153
Reviewer Key: A=Architect F=Fire&Life Safety S=Sanitarian M=Mechanical/Electrical
Ats
• •
VALLEY HOSPITAL
Chapter 246-320 WAC Hospitals
New boiler plant •
Plan Review Comments
9 o
e a
S ¢ z
F 1 0 Sprinkler system working plans shall be submitted for approval before any equipment
. is installed or remodeled. Deviation from approved plans will require permission.
Working plans shall contain all data as indicated in Section 1-9.2,Uniform Building
_ __Code Standard No. 38-1. _Plans and specifications, including hydraulic calculations,
that are incomplete or are not stamped by a Washington State Licensed Fire Spriticler— -
Contractor, will be returned without review. Plans and specifications may be submitted
separately from construction documents during the construction of the project. Sec.
1001.3,Uniform Fire Code 4/4/01
F 2 0 Complete plans and specifications for the fire alarm system installation or modification
shall be submitted for review and approval prior to system installation. Plans and
specifications shall include,but not be limited to, a floor plan;location of all alarm-
initiating and alarm-signaling devices; alarm-control and trouble-signaling equipment;
annunciation; power connection;battery calculations; conductor type and sizes; voltage
drop calculations; name, address, and phone number of the agency receiving off-
premises transmission of alarm; and the manufacturer,model numbers and listing
information for all equipment, devices,and materials. Incomplete plans and
specifications will be returned without review. Plans and specifications may be
submitted separately from construction documents during the construction of the
project. Sec. 1001.3, Uniform Fire Code 4/4/01
3 CI The DOH/CRS Architect has reviewed this project for compliance with applicable
regulations and codes and has no review comments. 4/16/01
4 The DOH/CRS Engineer has reviewed this project for compliance with applicable
regulations and codes and has no review comments. 4/16/01
5 El The DOH/CRS Sanitarian has reviewed this project for compliance with applicable
regulations and codes and has no review comments. 4/16/01
Page 3 of 3 Plan Review Comments for Project#6153
Reviewer Key: A=Architect F=Fire&Life Safety S=Sanitarian M=Mechanical/Electrical