1979, 08-06 Fire Hydrants, Flow5POISANFI VAL,I,F,ZI . FIRE DI IWtRTPU NT --�
EAST 10319 SPRAGUE AVE. • SPOKANE, WASHINGTON 99206 • TELEPHONE (509). 928-1700
Feldman Person Inc.
Attention: Stu Deysenroth
N2206 Pines
Spokane, Wa. 99216
COMPLEX Feldman Person for Keith & Jim Allan
COMPLEX ADDRESS El2400
BUILDING PERMIT: #
PLAN CHECK: #
Olive Ave.
August 6, 1979
The required fire flow for this complex is\\ 1750 - GPM.
\\
This complex requires 2 fire hydrant(s) to be installed.
t
The hydrant(s) shall be fnstalaed as, per approved water plan and
shall,be installed prio o^construction of complex.
Each hydrant shall be'capa of`flowing\a minimum of 1,000 GPM
at 20 PSI residual.e4ghennanjr2ihhydrants are'flowing'simultaneously.
The bottom of the joyest<outlet of the hydrant shall be no less
than 18 inches above finished` grade , \
Credit is given f r 'therftreJhydrant -at Olive apd Co
N.
i •
fry
/ /
f
DR:-s J
C.rt. County Fire Marshal
County Building Permit
Modern Electric