2008, 01-17 Permit App 07004542 Set MHApplication
THIS IS NOT A PERMIT
Penalties will be assessed for commencing work without a permit
Project Information:
Permit Use: SET 1975 34 X 48 COLUMBIA MFH Contact: KEITH MYERS
Address: 8709 E VALLEYWAY
C - S - Z: SPOKANE VALLEY, WA 99212
Phone: (509) 891-2680
Group Name:
Site Information: Project Name:
Plat Key: 002144 Name: REMINGTON PARK, AMENDED MAP District: Sout
Project Number: 07004542 Inv: I
Setbacks: Front 15 Left: 5 Right: 15 Rear:
Parcel Number: 35241.3324
SiteAddress: 422 S PARK RD
Location:: CSV
Block: Lot:
Owner: Name: KEITH MYERS
Address: 8709 E VALLEYWAY
SPOKANE VALLEY, WA 99212
Zoning: UR-7 Urban Residential-7
Water District: 020 EASTSPOKANE Hold: ❑
Area: 1,045.00 Acres Width: 67
Nbr of Bldgs: 1 Nbr of Dwellings: 1
Review Information:
Depth: 135 Right Of Way (ft): 60
Date: 1/17/2008 Page 1 of 2
Review
Building Plan Review
Released By:
Potable Water Review
Originally Released: 1/17/2008 By: NBENTLE
Released By:
PER EAST SPOKANE WATER DISTRICT
Originally Released: 11/19/2007 By: jdavis
Landuse/Zoning/HE Conditions
Released By:
Mobile home is pre-existing. Permit is to bring MH into compliance.
Originally Released: 1/17/2008 By: mpalaniuk
Operator: JD Printed By: JD Print Date: 1/17/2008
Project Number: 07004542 Inv: 1
Application
THIS IS NOT A PERMIT
Penalties will be assessed for commencing work without a permit
Sewer Review
Permits:
Date: 1/17/2008 Page 2 of 2
Released By:
Originally Released: 11/19/2007 By: jdavis
Contractor: OWNER
Item Description
INSPECTION FEE
Manufactured Home
Firm: OWNER
Phone: (000) 000-0000
Units Unit Desc
1 # SECTIONS
Fee Amount
$50.00
Permit Total Fees: $50.00
OLD PERMIT #07000375 WAS CONVERTED TO NEW PERMIT #07004542.
MANUFACTURED HOME ALREADY PRE-EXISTING.
MR BREZA CALLED ON 8/7/06 ASKED ABOUT A MOBILE HOME PERMIT APPLICATION,
LET HIM KNOW THAT WE HAVE A PACKET HERE AT THE OFFICE THAT WILL HELP HIM
WITH THAT PROCESS. HE CAME AND GOT THE PACKET AND TOOK IT HOME TO
COMPLETE THE SITE PLAN AND APPLICATION-JM
Received new complaint, file' forwarded to Legal Department on 03/O1/2007. Refer future complaints and inquiries to Legal Dept.
BRIAN BREZA, SON OF ZAN BREZA, CALLED TO FIND OUT INFORMATION ON WHAT
NEEDS TO DONE TO GET THIS PERMIT ISSUED. LEFT MESSAGE FOR HIM TO REFER TO
LETTER DATED 3-7-07 FROM MARY KATE MARTIN-JM
Payment Summary:
Permit Type
Manufactured Home
Fee Amount Invoice Amount Amount Paid Amount Owing
$50.00 $50.00
$50.00 $50.00
$0.00 $50.00
$0.00 $50.00
Disclaimer:
Submittal of this application certifies the owner (or person(s) authorized by the owner) has both examined and finds the information
contained within to be true and correct, and agrees that all provisions of laws and/or regulations governing this type of work will be
complied with. Subsequent issuance of a permit shall not be construed to be a permit for, or an approval of, any violation of any of
the provisions of the code or of any other state or local laws or ordinances.
Signature:
Operator: JD Printed By: JD Print Date: 1/17/2008
Site Address• 422 S PARK RD
Parcel Number: 35241.3324
Zoning: UR-7
Fire District: FD 01
Project
Transmittal
City of Spokane Valley
Community Development
Department
11703 E. Sprague Ave, Suite B3
Spokane Valley, WA 99206
Phone: 509.688.0036
Nev project ❑
Previous pre-app meeting
Plan revisions t,
Transmittal Date:
Wednesday, December26, 2007
Project Number: 07004542
Water District: EAST SPOKANE
Applicant: KEITH MYERS Owner: KEITH MYERS
8709 E VALLEYWAY 8709 E VALLEYWAY
SPOKANE VALLEY, WA 99212 SPOKANE VALLEY, WA 99212
(509) 891-2680
e-mail:
Contact: KEITH MYERS
8709 E VALLEYWAY
SPOKANE VALLEY, WA 99212
(509) 891-2680
e-mail:
Contractor: OWNER
( ) - 0
e-mail:
Occupant:
e-mail:
Arch ?Engineer:
e-mail: AND NORTHWEST ENGINEERING
Project Description: SET 1975 34 X 48 COLUMBIA MFH
Building
Landuse
Engineer
Utilities
Health
Fire Dist
Assessor
ENGINEERED PLAN
s.
Please send all plan review and project comments via e-mail to the
highlighted individuals.
Edit Confirmation
Page 1 of2
PAIRS Version 1.1.50.0 Logged into Production as HALPAIN, KAY
Confirmation
Permit FP1375056 Manufactured/Mobile Home
NSF L.CRS L IOT I__C IP
Purchaser
Contractor ID
Company Name
Last Name
First
Address
City
Phone
Site
Information
Site Owner
Last Name
First
Address
City
Location
Phone
Description
Notes
Directions
Power Company
BREZA
ZAN
8607 E VALLEY WAY
SPOKANE
(509)891-2680
VOID
Print Request
StatusActive
Applied 1/31/2007
Expiration 1/31/2008
StatefwA j Zip 92121
BREZA
ZAN
422 S PARK RD
Spokane
SPOKANE
(509) 891-2680
State
Not In The City
# Reqs
# Insps
Created inaIy235
1/31/2007
10:38 AM
Updated jhaly235
11/31/2007 j
REPLACE OLD DOOR WITH NEW ONE
EAST ON 5TH TO PARK GO NORTH TO #422
Services
Description
Quantity Amount
Structural` - OTHER STRUCTURAL CHANGES
• Total Cost
Total Paid
Total Due
$74.301
$74.30j
$74.30
$0.00
ew,Permltb
http://scsd.apps-inside.lni.wa.gov/pairspetmit/fimEditConfirmation.aspx?SmsgId=541557&SmsgSender= .. 1/31/200
Page 1 of
Contractor Name
Purchaser's mailing address
8607 E VALLEY WAY
SPOKANE
Telephone number
(509) 891-2680
Premises owner's name
BREZA, ZAN
Address of inspection
422 S PARK RD
Spokane
POST ON JOBSITE PRIOR TO BEGINNING OF WORK
License Number
WA 99212
FAX Number
()-
FAS ALTERATION PERMIT#FP1375056
Installation Description:
REPLACE OLD DOOR WITH NEW ONE
Services to inspect
Description
tructural- OTHER
TRUCTURAL CHANGES
Inspection fee: $74.30
This permit expires in one (1) year from date of last activity.
Applied: 1/31/2007 Expiration: 1/31/2008
MECHANICAL
Type
ELECTRICAL
Type
OTHER
Type
Inspection Date
Date Approved By
PLUMBING
Type
STRUCTURAL
Type
OTHER
Type
Quantity Amount
1 r $74.30
Date Approved By
Area, Building or Equipment Inspected Action Taken Inspector
Property Owner: This is your permanent record of inspection
http://scsd.apps-inside.lni.wa.gov/pairspernut/rptFASPernut.aspx7AppID=102
1/31/200;
Page 1 of
Receipt
Washington State Department of Labor and industries
Customer: ZAN BREZA
Address: 8607 E VALLEY WAY
City: SPOKANE State: WA Zip: 99212
-- Fiscal Transaction Receipt --
Fiscal Transaction: 101553462
Created: 1 /31 /2007
Payments: $74.30
Type
Check
-- Payments —
Amount Payer Reference
$74.30 ZAN BREZA 7233
-- Services --
FP1375056
Description Reference
Structural* - OTHER STRUCTURA FP1375056
Quantity Price
1 $74.30
F--_
NOTE: All refund requests must be made in writing. Refunds may require processing
through central office and we cannot guarantee immediate refunding of services.
http://field-services.apps-insidelni.wa.gov/FrontCounter/FCRevRecWeb/PConfirmPage.Aspx?AppID=2... 1 /31 /200
Plan Review Evaluation Information
Date: 1/15/08
Permit No# 07004542
Name of Site: Relocated Manufactured Home
Address: 422 S. Park Rd.
Use of Building: R-3
Type of Construction: VB
Fire Suppression System: No
Floor Area
1st Floor: 1,390 sq. ft.
Occupant Load
1st Floor: 6.95
Roof Height Eave: Peak: N/A
NREC: WA State
HB 1848 All Weather Protection: N/A
Other Conditions: Old permit #07000375 was converted to new
permit #07004542. Manufactured Home already pre-existing.
Plan Reviewer: Nik Bentley
SPOKANE COUNTY
DEPARTMENT OF BUILDING & PLANNING
1026 WEST BROADWAY AVENUE • SPOKANE, WA 99260-0050
SPoxt CouN Y
Site Information
Project Information
Site Address: 422 S PARK RD
Parcel Number: 35241.3324
Subdivision: REMINGTON PARK, AMENDED MAP
Block: Lot:
Zoning: UR-7 Urban Residential-7
Owner: MYERS, KEITH
Address: 422 S PARK RD
SPOKANE, WA 99212-0546
Building Inspector: MARK WALKER
Water Dist: EAST SPOKANE
Project Number: 07007863 Inv: 1 Issue Date: 11/14/2007
Permit Use: SEWER CONNECTION - EMPIRE HEIGHTS
Applicant: MYERS, KEITH
422 S PARK RD
SPOKANE, WA 99212-0546 Phone: (509) 981-5156
Contact: MYERS, KEITH
422 S PARK RD
SPOKANE, WA 99212-0546 Phone: (509) 981-5156
Setbacks - Front: Left: Right: Rear:
Group Name:
Project Name:
IPermits
Sewer Connection Permit Contractor: OWNER License #: OWNER
SEWER CONNECTION 1 $85.00 PROCESSING FEE 1 $15.00
Total Permit Fee: $100.00
FOR SEWER INSPECTIONS CALL THE UTILITIES DEPT AT (509) 477-3604 FROM 8:30-5:00 MONDAY-FRIDAY PRIOR TO
COVER. ONE WORKING DAY NOTICE REQUIRED. PERMIT ALLOWS FOR A 30-MINUTE INSPECTION. ADDITIONAL
INSPECTION FEES APPLY AFTER 30 MINUTES.
THE INSTALLER IS RESPONSIBLE TO INSURE ALL WASTEWATER DRAINS ARE CONNECTED TO THE SEWER AND
MAY BE REQUIRED TO PERFORM TESTS FOR VERIFICATION. INSTALLER IS TO FIELD LOCATE AND CONFIRM THE
ELEVATION AND POSITION OF SEWER STUB PRIOR TO ANY OTHER EXCAVATION.
SEWER STUBS ARE TO BE CHECKED PRIOR TO CONNECTION TO ENSURE THAT THEY HAVE ACCEPTABLE GRADE
AND ARE CLEAR AND UNOBSTRUCTED TO THE MAIN. SEWER LINES SHOULD BE CONSTRUCTED TO ALLOW FOR
GRAVITY FLOW FROM THE LOWEST LEVEL OF THE STRUCTURE.
THE INSTALLER AND THIS PERMIT MUST BE PRESENT AT THE JOB SITE AT THE SCHEDULED INSPECTION TIME.
BOTH STATE LAW RCW 19.122 AND COUNTY CODE REQUIRES. THE INSTALLER TO GIVE NOTICE OF EXCAVATION TO
OWNERS OF UNDERGROUND FACILITIES.
CALL 1-800-424-5555 BEFORE YOU DIG --AT LEAST 2 WORKING DAYS IN ADVANCE. SPOKANE COUNTY CODE
REQUIRES THE INSTALLER COMPLY WITH ALL REQUIREMENTS OF THE WA STATE DEPT OF LABOR & INDUSTRIES,
INCLUDING THOSE RELATED TO TRENCH SAFETY.
Payment Summary
Total Fees AmountPaid AmountOwing
$100.00 $100.00 $0.00
Tran Date Receipt # Payment Amt
11/14/2007 6679 $100.00
Processed By: Hargrove, Heidi
Printed By: Lemley, Linda Page 1 of 1
PERMIT Y:
RECEIVED BY
CITY OF SPOKANE VALLEY
NOV 1 4 2001
PERM CENTER
A LC- tel
1f
5 Po'.- I' IA1h - i - t
Fob
t%
I•2X2L-
r X 1ST,
s
c is -5 i;.; LL c_ r3E
ZCrArt- oL--,i
A- •-re+c= 7bc -
I
ov L — i&Th
it
t,z-ia 1
ll1 or-ACiU�f2�b a' `—c'�Fc6A—�ce�k-rtsxiEGi
' � N per P i
E. Le,t..K._ . .{'._t kJ' c r 4\ 1
• ii
g `) NEC-0' Pr -1)ESI f 1 ?act=t1:5"- N ',-,- ti-to:ne-
cX fTr CJ )
s_S �
PLANNING DE1424.
.3ti &ED
BY:
DATE:
/%i7/2Go7
LZ
ri.)r_rin
1ox yo,
PAR k: R.t>
1 tJ
1 7"
CCV(5-g.L.i-)1
OK.) -'Scp ! 2.A-TE
f
1
N1 5 SEte
i
LJ
PAR.K RD
eland
orthwcst
MI Engineering, Inc.
Keith Myers
422 South Park Road
Spokane Valley, WA 99212
Tapio Office Center, Green Flag Building
104 South Freya Street, Suite 110-F
Spokane, WA 99202
(509) 532-1532 Voice and Cell, (509) 534-0664 Fax
December 20, 2007
RE: Myers Investigation, 422 South Park Road, Spokane Valley, Washington
Project Number. 2007249
Dear Keith,
We have reviewed the site conditions and foundation construction of the above referenced structure.
The triple -width manufactured home is approximately 50'-4" x 10'-1" x 7'-0" side wall height plus 40'-3" x
22'-9" x 7'-6" side wall height with 4" fascias and floor 1'-6" to 3'-9" above grade. There is a site built
attached 9'-0" x 4'-0" covered porch at the front door and a site built attached 16'-0" x 4'-0" deck under a
independently supported 26'-0" x 14'-0" roof at the rear door.
The foundation system consists of 1'-4"x8" to 1'-4"x4" to 3'-4" tall un-reinforced masonry piers
supporting the main floor beams at 4'-0" to 8'-0" on center and under the inside corners. These piers
are supported on individual solid concrete masonry pad footings. There is a plastic perimeter skirt wall
extending to soil at grade partially surrounding the crawlspace. There is no anchorage to prevent
longitudinal, transverse, uplift and overturning shifting of the manufactured home off the foundations. A
vapor barrier is only partially in place.
This foundation does not comply with the U.S. Department of Housing and Urban Development
Permanent Foundation Guide for Manufactured Housing HUD-007487, dated September 1996 (update
of Handbook 4930.3, August 1989, incorporating Handbook 4145.1 REV-3 Change 1, February 14,
1992). The footings are suitable for the soil, climate and geological conditions of the site, are able to
support the size and weight of the manufactured home and meet Federal, State and local laws, rules
and regulations. Placards (not observed) on ends indicate units were constructed after June 1976 to
U.S. Department of Housing and Urban Development and Federal Home Construction and Safety
Standards.
To achieve compliance with the standards and regulations referenced above, 31'-0" x 1'-8" x 8"
transverse or Two-15'-6" x 1'-8" x 8" longitudinal concrete footings reinforced with 2-#4 longitudinal
bottom bars must be installed at each end. Anchors must be installed to provide a minimum of three
longitudinal pairs and four transverse pairs of bracing with a capacity of 3150 lbs. in each direction. This
bracing is commonly installed as pairs of diagonal tension only 1 '/4' x 14 gage straps (Minute Man or
equal) installed in an "X" or opposing diagonal configuration. Longitudinal bracing extends from the
bottom of a floor beam at a low slope 3'-0" of more horizontally to a footing under the same beam.
Transverse bracing extends from one floor beam to a footing under the adjacent beam or just inside the
skirt. These anchors are best attached to the beams and footings near the piers. These straps are
generally connected to the beams and footings with specially made devices and all elements of this
system must be rated for the specified force at the angle of installation.
Additionally, missing portions of the perimeter walls around the crawlspace must be replaced with
preservative treated plywood or plastic extending from soil surface to the rim joist. The bottom of the
wall may be braced with diagonal struts to the floor framing or with steel spikes into the ground. A
masonry, concrete or bottom bearing wood wall must be supported by footings at 2'-0" below finished
exterior grade. Piers consisting of 4x4 preservative treated posts or 8"x8"x1'-4" concrete masonry units
must be installed under the interior edge of the front porch, the interior edge of the rear deck and the
inside comers at the intersection of the double wide portion with the single wide portion. These piers
must be supported by 8"x1'-4" minimum footings located 2'-0" below finished grade.
d
co CD
o
a
N
a c
m
N
..
a
IL
ri) —
0
N
O
cD
C
(D
N
O
N
O
O
v
Site built
covered
porch
to remain./
Pl.
P1.
C
. 1
J
r-
Longitudinal
anchors six
places. Opposing
diagonal configuration
(shown this end) an
'X' configuration
(shown opposite
end) must be used
both ends the same,
P1.
C
Axis of symmetry' Footing
7-
and anchor configuration
as shown either end
must be mirrored about
centerlines.
F-
▪ L
I-
▪ L
r
Reconstruct
- perimeter -
wall as
required. _ 1
L
7
J
NOTE' Manufactured
anchor systems may
be substituted for
footings and anchors
upon our approval of
techrljcal . "Submittals.
Or a'144
Odo,c�,�`,iSCc� n
TSJOti.FLS1.2
s 2e:•=s1
31'-0' x 1'-8' x 8' footing
transverse (shown this end)
or three 15'-6' x 1'-8' x 8'
footings longitudinal (shown
opposite end) with 2-#4
longitudinal bars each end.
Axis of symmetry' Footing
and anchor configuration
as shown either end
must be mirrored about
centerlines.
P1.
P1.
Attached
deck to
remain.
Roof -to
remain.
P1: (Six places) Provide 4x4
preservative treated Number
Two Hem -Fir post or 8'x8'xl'-4'
masonry block pier on 8'xl'-4'
x4' minimum concrete footing
2'-0' minimum below grade.
Transverse anchors
eight places. Opposing
diagonal configuration
(shown this end) or 'X'
configuration (shown
opposite end) must be
used both ends -the same.
PRIMARY FOUNDATION PLAN
v
NORTH
REVISEINS
BY
Wood
`\ordnvtartt
8nginecrinq. Inc.
POffice Center, Green Flag Building
104 South Freya Street, Suite 110•F, Spokane, WA 99202
,(509)532-1532 Voice and Cell.(509) 534-0684 Fax
Myers Residence
Foundation Improvements
fig' = 1'-0'
BRIT DANIELSON
422 South Park Road
Spokane Valley, Washington
maxim
2007249
'""
December 20, 2007
Wrap Around
Strut At Beam
Foundation
Bolt
Bolt to Connector
Plate or Bracket
Footing,
See plan.
`Chassis
Beam
Anchor —
"X" CONFIGURATION
Or Wrap Around
Strut At Beam
OPPOSING DIAGONAL
Or Bolt to
Connector
Plate or
Bracket
Anchor
Foundation
Bolt
LONGITUDINAL ANCHORAGE
r� Chassis Wrap Around r I1
Beam Anchor Beam jJ
Existing — — Foundation
Pier
Bolt
"X' CONFIGURATION
LJ
1 t—
Wrap
Around
Beam
Foundation
Bolt
_Chassis
Beam
Anchor
Existing
Pier
Footing,
See Nlun.-
OPPOSING DIAGONAL
TRANSVERSE ANCHORAGE„
Opposing diagonal or
'X' configuration may
be used
interchangably as
conditions permit.
Longitudinal anchors
may be located at
any point along the
length. One
longitudinal pair must
be located at each
exterior beam..
Transverse anchors
should be
symmetrically placed
about midlength with
first pairs within
10'-0' of each end.
REVISIONS
BY
I Noland
`
Tapia t
Engineering. Inc.
Office Center. Green Flay Butdlrg
104 South Freya Street. Suite 110-F. Spokane, WA 99202
,(509)532.1532 Voice and Cell,(509) 534-0684 Fax
Myers Residence
Foundation Improvements
aia• = 1'-0•
s p
sRETT DANIELSDN
422 South Park Road
Spokane Valley, Washington
JD MOM
2007249
a""
December 19, 2007
Permit Center
*Wane
61000\11703 E Sprague Ave, Suit-.jVley" (509)688-0036 FAX: (50 EIVED BY
Spokane Valley, WA 992
F SSPOKp,NE VALLEY
` 68�8-0037
www spokanevalley.org
Community Development
Manufactured Home
Permit Application
PERMIT NUMBER:
PERMIT FEE:
PERM T ENTER
BY:
IN OTHER e
SITE ADDRESS:
ASSESSORS PAR
4-2? 5: �s9k, R. 5&o,..4/ J
urr ) fir: if3 0 1_074
CEL NO: LEGAL DESCRIPTION:
Building Owner:
Name:
we Tom( 1_ . y�,-r, c
Address: �/2,_ 6✓
n 2.2
.
City: r7"ok/4 �6 YALL9 State: Zip. l
l t/q
Phone:so, ^ y�I_ x IS13Fax:
Contact Person
Name:
Phone: ,50—qX/-L5753
Contractor:
T
Name:
Address:
City:
State:
Zip:
Phone:
Fax:
Contractor Lic No:
Exp Date:
City Business Lic. No:
Describe the scope of work in detail: SC 1 pri) 1TJ171aI)7g-
T Pee. ' Y Seerii
MANUFACTURED HOME
Width: 34,'r
Length: 4e /
Year:
Manufacture: C OG.u/r7,e3/09
Previous Address: 4.2..2 5. e 2.
Proposed Use: J/;,.16z.g. /5 PP /2-7 j) hi LL/A/4,
Pit Set A/
Septi ewer)
The permitee verifies, acknowledges and agrees by their signature that: 1) If this permit is for construction of or on a dwelling, the
dwelling is/will be served by potable water. 2) Ownership of this City of Spokane Valley Permit inure to the property owner. 3) The
signatory is the property owner or has permission to represent the property owner in this transaction. 4) All construction is to be done
in full compliance with the City of Spokane Valley Development Code. Referenced codes are available for review at the City of
Spokane Valley Permit Center. 5) This City of Spokane Valley Permit is not a permit or approval for any violation of federal, state or
local laws, codes or ordinances. 6) Plans or additional information may be required to be submitted, and subsequently approved before
this application can be processed.
Signature
Method of Payment:
❑ Cash
Bankcard #:
Authorized Signature:
REVISED 8/23/2005
❑ Check
❑ Mastercard
Expires:
Date l //l-//07
❑ VISA
VIN#:
Spokane
lley
For City Use Only
PLUS Project Number (710
�
Project Address 477 �r;c{
11703 E Sprague Ave Suite B-3 • Spokane Valley WA 99206
509.688.0036 ♦ Fax: 509.688.0037 ♦ permitcenter®spokanevalley.org
As part of our on -going commitment to customer service during the review process of your project
application, we are providing you with a TARGET DATE for the initial technical application review. If for
any reason we cannot meet this date, we will contact you with a revised tarrget date.
Your application review TARGET DATE is j\) () (irk KKQo c)
The TARGET DATE is the date we estimate your project application will have had its initial technic
review. It is not the date for approval or permit issuance.
Tips for a Smoother Project Application Review
Submit complete, accurate plans and documents.
Extra time may be required for re -submittals as project application reviewers work on multiple applications and it
may be several days before they can look at your new or revised information.
i Designate a specific contact person to communicate with the City.
While the person designated as the applicant's contact person with the City can be changed, one individual with the
expertise for dealing with reviewer comments would be the best choice for the entire review process.
i Call staff regarding the status of your project only after the target date shown at the top of the page.
Although you should be contacted on or by the target date, please feel free to contact us if you haven't heard from us
by your target date. Staff may contact you before the target date if the initial review is complete. By following this
procedure, you will save time and allow the reviewers to complete the work more expeditiously.
Steps in the Permit Process
1. Counter Complete. Your application has been accepted as counter complete. This means all of the required
documents, as indicated on your Pre -Application Checklist have been submitted or have been approved for deferred
submittal. This does not prevent technical staff from requesting additional information as a result of their technical review.
2. Quality Check. The next step in the process is a quality check to make sure that the application is reviewable and free
from substantive flaws that would prevent technical staff from completing the technical review once it is started. When
this step is complete, your application will be routed to the appropriate staff and remain in their review queue until it
comes up for review.
3. Technical Compliance. Once an application is administratively complete, it is routed to technical staff for compliance
review. Depending on the type of project, technical staff may include multiple reviewers. You should be contacted by
phone, fax, email, or mail by your TARGET DATE once the initial technical compliance review is complete.
4. Permit Issuance. When the technical compliance review of the application is complete, including any subsequent re -
submittals, each reviewer will approve their section of the application and route it to the Permit Center. When all sections
of the application are received, a Permit Specialist will process the application and contact the person specified on your
application for permit pick-up. Information regarding fees and pre -construction meetings (if required) will be provided by
the Permit Specialist at that time.
WHITE —APPLICANT PINK — BUILDING FILE
REV 9/07