1998, 06-22 Field Inspection ConcernsBUILDING AND PLANNING •
DAMES L. MANSON, C.B.O., DIRECTOR
Mitchell & Lucenette Hicks
5920 E 96 Avenue
Spokane, WA 99212
A DIVISION OF THE PUBLIC WORKS DEPARTMENT
DENNIS M. SCOTT, P.E., DIRECTOR
June 22, 1998
Re: CHANGE OF USE TO KINDERGARTEN
Dear Mr. & Mrs. Hicks:
The following comments are based on my field inspection of 6/19/98. Items listed are
concerns or requirements of the Uniform Building Code (UBC) and do not reflect
requirements or conditions required by other rules, regulations or codes enforced by
Spokane County or other jurisdictions. Do not consider these comments a plan
review or minimum requirements for the proposed use. These comments should be
forwarded to your professional design consultant for his / her use and information.
1. The new use shall be classified as a Group E-2 in accordance with the U. B. C. See
U. B. C. Section 305.1.
2. The maximum occupant load of this building shall be 49 persons.
3. One accessible parking space shall be provided. It shall be the closest parking space
to an accessible entry. See WAC 51-30 Chapter 11, Section 1107 for design standards.
4. All rooms used for sleeping should have a means of emergency escape or rescue.
The emergency door or window should be operable from the inside to provide a full,
clear opening without the use of separate tools. See U. B. C. Section 310.4.
• 5. Doors shall have landings on both sides. Provide a landing on the garage side of
the door between the garage and kitchen area. See U. B. C. Section 1004.
6. Please provide as much construction detail for the existing retaining wall as is
available.
• 7. Please verify that all glazing meets the minimum requirements for safety glazing as
required by U. B. C. Section 2406.
1026 WEST BROADWAY AVENUE • SPOKANE, WASHINGTON 99260
PHONE: (509) 456-3675 • FAX: (509) 456-4703
TDD: (509) 324-3166
• 8. The main level (main entry level) shall be made an accessible level. Provide wheel
chair access to the main level. The accessible entry may be an entry through the
converted garage. Provide a ramp for access to the remainder of the main level. See
WAC 51-30 Section 1106.8.
9. All walls of E-1 occupancies that are less than 10 feet and more than 5 feet from a
property line shall be not less than one -hour fire -rated assemblies. Openings in such
walls shall be not less than one -hour fire -rated assemblies. Provide details of the
required fire rated assemblies.
10. All guardrails shall be not less than 42 inches high. Open guardrails shall have
intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter
cannot pass through. All existing guardrails and hand rails shall meet the minimum
standards of the 1994 U. B. C. See Sections 509 and 1006.
11. Not less than one toilet facility shall be fully accessible. The accessible facility
shall be located on the main level. See WAC 51-30 Section 1106.
These comments do NOT constitute a comprehensive plan review. A complete plan
review will be done when a permit application is requested. and comprehensive plans
are received (provide two sets). This additional review may require changes in the final
building design.
Please submit revised plans for the above listed items. The drawings shall have
sufficient detail to confirm compliance with the appropriate codes as enforced by this
jurisdiction. Your immediate attention to the items above is appreciated. Should you
have any questions, please contact this office between the hours of 8:00 a.m. and 4:00
p.m. weekdays.