1990, 04-13 SVFD Fire Flow Ltrr • 411 SPOKANE VALLEY FIRE DEPARTMENT Spokane County Fire Protection District No. 1 EAST 10319 SPRAGUE AVE • SPOKANE, WA 99206 (509) 928-1700 Rod Tedrow Chief Spokane County Building Codes W. 1303 Broadway Spokane, Wa. 99260 Re: E. 12614 Sprague Ave. White Elephant #2 April 13, 1990 L. 1\g SPOKANE_ COUNTY BUILDING CODES DEPT. 1. Fire flow for this building is 2250 G.P.M. 2. Two new fire hydrants will be required to be installed. One new fire hydrant and the Fire Department connection will be required to be located on the South side of Sprague Ave. at the East property line. The second fire hydrant will be lcoated at the Southeast corner of the building. Fire hydrant locations shall be as per an approved water plan approved by the Fire Department. 3. As per Uniform Fire Code 10.309, central monitoring will be required for the sprinkler system. 4. Access to the back of the building needs to be addressed for Fire Department and emergency vehicles 5. A Knox Box entry system will be required. CW/bd ;Clyde Wisenor Inspector II GUIDE FOR DETERMINATION OF REQUIRED FI411 RE FLOW • 4/1- FIRE DISTRICT 11 01-4 DDRESS a&141 F A PLAN 11 -- Via►,. DETERMINE TYPE OF CONSTRUCTION - CLASS (CIRCLE ONE): I - II IV FIRE -RESISTIVE NON-COMBUSTIBLE NOTE: IF DETERMINE DETERMINE III ORDINARY 1,0 V WOOD FRAME MIXED MIXED`, SEE SPECIAL INSTRUCTIONS FOR AREA AND BASIC FIRE FLOW. THE GROUND FLOOR AREA rim 1/3(1,i1)0216)(00)'F."= 51220 THE HEIGHT IN STORIES M (C11-I. rvI-E' .-Z // DETERMINE REQUIRED FIRE FLOW TO THE NEAREST 250 GPM (USE TABLE 37 GPM DETERMINE THE CREDIT OR SURCHARGE, IF ANY, FOR TYPE OF OCCUPANCY. IF OW HAZARD, SUBTRACT UP TO 25% OF (D); IF HIGH HAZARD, ADD UP TO 25% OF (D) CREDIT (SUBTRACT) SURCHARGE (ADD) r^t 1 S" TOTAL1001�122CJ TERMINE CREDIT IF ANY FOR AUTOMATIC SPRINKLER PROTECTION. CREDIT (SUBTRACT)�o TOTAL I(1O DETERMINE EXPOSURE ADJUSTMENT;' USING THE TABLE AT LEFT AS GUIDE, ENTER THE SEPARATION AND ADJUSTMENT FOR EACH OF THE 'FOUR FACES' OF THE BUILDING IN THE TABLE AT RIGHT: SEPARATION MAX ADJUSTMENT EXPOSURE 0-10 25% MAX .11-30 20% Max 31-60 15% MAX 61-100 10% MAX 101-150 5% MAX 151-oR 4-HR WALL 0% MAX NORTH EAST SOUTH WEST TOTAL % ADJUSTM T (NOT TO EXCEED /3%): DETERMINE ROOF COVERING ADJUSTMENT; (IF WOOD SHINGLE ROOF COVERING, ADD 500 GPM) ACT. ADJUSTMENT ADD % ADD ID % ADD - 0 % ADD 2S % 41 % ADJUSTMENT: i•,IDkIG (G) a (H) SURCHARGE (ADD) "721 TOTAL: 23.4) OFF THE FINAL ANSWER TO THE NEAREST 250 GPM IF LESS THAN 2500 GPM AND NEAREST 500 GPM IF GREATER THAN 2500 GPM, TOTAL REQUIRED FIRE FLOW: 21 50 .,.I l.. III II WI a TO