2006, 02-02 Bldg A: Material & Test Report Aboveground Piping FROM PATRIOT FIRE PROTECTION, INC. (THU) APR 20 2006 14 :03/ST. 14 :00/Na. 6834436680 P 20 PRE PROTEATR1OT CTION CONTRACTORS MATERIAL&TEST REPORT FOR ABOVEGROUND PIPING ::,.a..e..,»x.x.....�,.x- r..,......... ... ................., ............,...........,.....,,....:.{a..�...,..,........._... �.- �r .._.......... ....w.c.r.�:.� :T;:...... PROCEDURE Upon completion oiwork,inspection and meta shall be made by the contractor's representative end witnessed by an owner's representative, Ali detects shall be corrected and system left In service afore contractor's perionnel finally leave the job. A artifloete shall Defined out and signed by both representatives. Copies shall be prepared Iv approving authorities,owners,and contractor. It Is under- stood the owner's representative's',Nature In no way prejudices any claim against contractor for faulty material,poor workmanship,or tallurs to comply with approving authority's requlrarriants or IOW ordinances. PRAY NAME (f - I °ATS l�-f ``DSO, PROPERTY ADD S$ So ddo ' fig „ ar 'gild, ` . .• T---a 9 `s'-r I k ( f` / l a11 . • I T- ION CONFORM T+ACCEPTED PLAN• r!L. IS NI PLANTS EQUIPMENT USED IS APPROVED "• ❑NO IF NO,p(fsLNN DEVIATIONS = P 49 a; IN C 'e E • FIRE EQUIPMENT BEEN INSTRUCTED AS TO L TI N YES N OF CONTROL VALVE AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? F NO,D(PLAIN HAVE eta' d_ a THE F• •WING BEEN LEFT • TH `-I I d-' M '1-' 11 N• INSTRUCTIONS 2. SYSTD COMPONENTS INSTRUCTIONS r YES ONO 2. CARE AND MAINTENANCE INSTRUCTIONS. - . DYES ONO i 3, NFPA 13A A OYES ONO °�' LOCUTION SYSTEM a v .� SERVES: .rir b _' — A Of SYSTEM f . KW MODEL .•►a QUANTITY 'RATING r ffirrI«i1•:a1TTt illiin YfiA=MIMIC' SPIi1NKr!R$ mood tr1r� � ,...� rrripm�:..:6∎E T`a_' • jl�`yIP' rr� . iI..rM ,fk PtPlr AND TYPE OF PIPE / & -' . . . • FITTINGS TYPE OF FiTTIN3$ Aralirmille9101111 '. .k. • i i AMU ALARM Dk'VICE MAXIMUM TIME TO OPERATE VALVE THROUGH TEST CONNECTION OR FLOW TYPE • - MODEl. MIN SEC. INDICATOR 7rlT1M‘ !'fi7#11=' 'i+ � TL S e_.. DRY VALVE MOO. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. i TIME TO -IP - TT' in-1T DRY PIPE THRU TEST WATER AIR TRIP POINT REACHED OPERATED OPEMT1ND CONNECTION PRESSURE PRESSURE MR PRESSURE TEST OUTLET PROPERLY TEST SEC. PSI PSI P. MIN. SEC. YES Q WITHOUT � WITH. MUM Ira, 0~1-■1 MEASURED FRIM TIME INSPECTORS TEST CONNECTION 1S OPENED SSA (OVER) FROM PATRIOT FIRE PROTECTIONr1NC. (THU)APR 20 2006 14:04/ST.14:00/No.6834436680 P 21 - OPERATION ❑PNEUMATIC ❑ EL€CTRIC []HYDRAULIC DELUQE PREACTION VALVES PIPING 6UP f SED YES NO DETECTING MEDLA UP 5ED Li YES Li N DOE VALVE NERATE FROM THE MANUAL TRIP AND /OR REMOTE CONTROL STATIONS UYES U NO ERE AN LSSIOLE FACILITY IN MH CIRWiT FOR TES Nei DYES 11 No IF NO, EXPLAIN DOES EACH CIRCUIT OPERATE OOtwS EA H CI UIT MAXIMUM TIME T MAKE MODEL SUPERVISION LOSS ALARM OPERATE VALUE RELEASE OPERATE RELEASE TEST DE8CF1IPn0N HYDROSTATIC; Hydroelallc testa shE01 N made at not lose than 200 pal (19,6 bare) ter two hours or 50 pal (3,4 bare above aiwic prosaure in pxtee86 f 160 pA (10,2 bus) 10; tvla hours OytereniksI d(y-plpa valve etappe(a shall be to It opan durina Ioat to prevent drrm'ga. Ali above, aroUnd piping Ieakap# Oil be lopped PNEUA14TlG; Ealebl lah 40 psi 12,7 be Ia) alr ptaaeuio and mesaure drop winch shall not exceed 1 -% pil (Q,1 bare) In 24 hptirs.Ye at preasura tanks al pnrM@I wata leval and Alf P19121ire gno manaure sir proaaure drop which shell nef oxgeed IVY yal (0,1 bare) In 24 hpure, ALL PIPING HYDFMTATrALLY TESTED AT 81 FOR H OW I � HNO l �S P EY EQUIIEW OPERATES ROPRL ❑ P y rdZ 55—YUU—MFIFY A5 THF-WRINKLER SYSTEM CONTRACTOR THAT ADpITWE AND RPIOSM CHEM 80011UM SILICATE OR DERNATIVES OF $ODIUM SIUCATE, ORtNE, OR OTHER coRRnrm CHT GALS WERE NOT USED FOR TEST. ING SYSTEMS OR STOPPING LEAKS? ❑YES ONO TESTS FEADM OF GArIE LOCATED NEAR WA �T NT I'r SUPPLY TEST ONNECTIONt � P91 CONNECTION OPEN WIDE 45 PSI UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISERU FLU$HItiD BEMIRE CONNECTION KME T SPRINKLER PIPINQ. EQ EIY COPY OF THE U FORM NO. 8513 OYES ONO QTKFA EXPLAIN FLUSHED BY INSTAL.EROF UNDER - ROUND SPRINKLER NPtNG ❑YES ❑ NO BLANK UMBER I 1AM LOCAT*NS NVAIPIER REMOVED GASK� PIP/ WYES Q NO IF YES.. . YOU CERTIFY AS T—HkVkNKLEFI CONTWTOR THAT WELDING PROCIEDU COMPLY THE REOUIMMENTS OF AT LEAST AWS D10.9, LEVtrI. AR-3 DYES ❑ NO WEL01Nd DO YOU GEFTTIFY THAT THE WELDING WAS PERFQRMF� BY WELDERS QUALIFIED IN MPLIANCE WITH THE REOUIREMENTS OF AT LEAST AW6 010,9, LEVELAR3 ❑YES ❑NO OQ YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A MEtr M QUALffY CONTROL PROCEDURE TO INSURE THAT ALL DISCS AAA E,VED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER NG RESIDUE ARE REMOVED, AND THAT THE INTERNAL D METERS OF PIPING AAR NOT PENE PATEO ❑YES ONO CU1bUT8 YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL IlsC OUTOUTS (0120 ARE RETFdEVVD7 OYES LINO PUNCTMNAI. FLOWrEST DOES AEU AIMVM A FUNCTiC}IVAL FLOW TEST OF RESIDENTIAL SPRINKLI_RS7 UYES UNQ WVtE FUNCTIONAL FLOW TEST RESULTS SATISFACTORY? ❑YES Q NO DATA NAMEPLATE NAME PLATE DED ❑Yr4S ONO ' EW LAIN REMARKS DATE LEFT IN $I* NrA WITH ALL CONTROL VALVES OPEN: ��► NiR141E NKLER OR A CONTRACTOR LICENSE'v PATRIFPOMF STS WITNESSED BY SI ®HATE R68 j TlTLI~ FOR SPRNKLE (SIG _ TIT DATE FOR AP#�RW4M40AITY �f r DATE CERVY THE INFORMATION HEREIN IS TRUE AND THAT THI INKIER SYSTEM WAS INSTALLED W ACCOROP ANGE WR H ACW 16.140 AND THE RULES ADOPTED BY THE WASHINGTON ADMINISTRATW CODE AS ADMINISTEnED BY CERTIFICATION E STATE FIRE MARSHAL fib\ M OF CERTLeOC ATE OF COMP15TENC3Y hOLDER (MINT OR TYPI,) °J174MATUM C++r CtR TIF)CATE OF" 0C4JVfrI5bW F OWO CERTIFICATE REGISTRATION 0 DATE Apq 106AL Eij' h Aaro NOTE VA UACK r- FROM PATRIOT FIRE PROTECTION, INC. (THU) APR 20 2006 14 :01/ST. 14 :00/N0. 6834436680 P 2 PATRIoT ,pc RE PROTECTION CONTRACTORS MATERIAL.&TEST REPORT FOR UNDERGROUND PIPING ...,,- EDURE ,71 ..�=�`_^ uz.. ......,,.,...:; :::-7.1..,......_x,,... • .....:e<w.iu„au.«n. .. . ..-.. ., -- -1 eR:'..-re Upon comptation01 work,InopeOdIon and testa email be mode by the cantrcctor's representative and wltn■sud by in owner's representative.All c ataefe*hell by corroded Ind ayetem loft In alnico before contractor',personnel tinally la 1Y1 Oa'ob. A vanillin ate chill by filled out and atoned by both iepra,onipile's,Copia,ehatl be prepared for epprovfno authorities,ewnerc,and oontrector,It I■understood the owner's rrpreasnlative'a etgnature In n0 way prafyplos•erg claim ag ah5*f eoAiraetor for faulty material,poor workmanahlp,or!allure to comply with epprovin9 authority's requtremenla or local Ordinances. PROP NAME , tj' � DATE r a . ! ►1 may, 1IwAI et 1 kp- 0 �6 •Y 7PEliTY ADDRESS I oC.�C��. 6r .1d iWil - d if �-►. �f �t A a jr L Y ACCEPTED BY APPFlOVI AUTHORITIE- (NAME) _ A134: -- PLANS IN AWITION C F RM ACCEPTED PLAN p EQUIPMENT USED IS APPROVED YES NO IF NO,E XPLMN DEVIATIONS HAS PER&)N IN CHARGE IF F1R •UIPM3T s INSTRU'-'s AS TO • -TION • '3- 111 NO OF CONTROL VALVE AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO,EXPLAIN . INSTRUCTIONS RAW-CONES t3F THE APPROPRIATE INST •N= AND AND Ir CE C ' . • 11 • BEEN LEFT ON PREMISES? IF NO,EXPLAIN • LOCATION PPLIES BUILDINGS 4 • _ ,q .1` • - AN a .V,{�'V TYPE JOINT • PIPE CONF•- S TO -'1'' ,•ni,43 " .e;i:, I YES U N• FITTINGS CONFORM TO . `� C ~ST,AN,*T t•'' •YES 0 NO UNDF_ROROUNI} N0,EXPLAIN- e"";•* �,. MPrEE r=`0.-,, AND JOINTS JOINTS NEEDING ANCHORAGE CLAMPED,•7 •PEL),OR Et* t='t IN •YES • I NO SCE WITH •'I'.` STANDARD IF NO EXPLAIN . a r+77 -6A y FLUSHING Flow flee required rate until water la clear es Indycoled by r o 1 lel foreign material In burlap bags at cutlet,iv*h u hydr{Ate and blow- dffe.Fluahet flows not Icuthan 300flPM for 4inahpipe, p ..� p pipe.094QPMforr'wln'eh� �, �PfAror6-Inch 1pe,2tS00PMfa1f}1nCh ! and 352t]OfM for l2-Inoh (...2 / y/'�� pipe,When/supply oennat produce ellpuiet,d flow rates,obtain mekhnirih ieailable. ti/l e' HYDROSTATIC Hydrao tat lo teat shall be made oh not lase than 200 pal for two hour•or 00 pal above italic pressure fn excaee of 1:0 NI for Iwo hour,. TUT N E�I�PTIO., LEAKAGE New pip,tiff with rubber geakt led!oldie shell,if the warkmanahlpIsosil Waste ry,have liffleornoleakegeatlhat itle.Tneamount0lleakageet the taints shell not exceed 2 qte,per hour per 100/cots lrreepeotve of pipe diameter.TM leakage thrill be dtslrlbuled over all pinta.If auch Itampa occur.at a taw lalnta the Inslellellen chill be con,iduad unsalief oratory and necessary repairs made,The amount of allOwiable tealreoe aneoltied above May be Inorauied by 1 If.or per In,v,lva diameter per.hour for each modal Rated valve Isolating Ma lest action,if dry barrel hydcante are healed with the mein vtlre open,PI the hydrants are under premium,an additional 5 or per minyte leakage Is permitted for each hydrant. f NEW UNDERGR.UND PIPING FLUSHED ACCORDING TO STANDARD •YES III NO �e tie/ T RY(COMPANY) IF NO,EXPLAIN • .H*W - U iN •T' •EITAIN + -- -r•q e(' Ty' • •'3 IF FLUSHING ' ( PUBUC WATER OTANK OR RESERVOIR 0 FIRE PUMP El HYDRANT BUTT Sid OPEN PIPE TESTS LEAD-INS FLUSHED ACC R1:31NG TO STANDARD YES 0 BY(COMPANY) IFNO.EXPLAIN HOW FLUSHING FLOW WAS OBTAINED ' THROUGH WHAT TYPE OF OPENING 0PUBUC WATER ❑TANK OR RESERVOIR 0 FIRE PUMP 0Y CONN.TO FLANGE&SPIGOT 0 OPEN PIPE ©'� OVER) FROM PATRIOT FIRE PROTECTION, INC. (THU) APR 20 2006 14 :01/ST. 14 :00/No. 6834436680 P 3 AU.NEW UNDERGROUND PIPING HYDROSTATICALLY TE 'D AT JOINTS CO RED HYDROSTATIC 4)0 PSI FOR Z, HOURS DYES ONO TEST TAL AMOUNT OF LEAKAGE MEASURED LEAKAGE - [GALS, HOURS TEST ALLOWAELE LEAKAGE - ��GALS, HOURS ItY[}FtANT NUMBS 1 TAEL FYP1:AND MAiCI: _ _ YES o Na WATER CONTROL VALVES LEFT WIDE OPEN _ YE8 N0 CONTROL IF NO,STATE REASON - VALVES H6SE THREADS OF FIRE DEPARTMENT NN TI AND HYDRANT INTERCHANGEABLE — WITH THOSE OF FIRE DEPARTMENT ANSWERING ALARM _ DYES C�NO N REMARKS • NAME• I = ALONG • RACTOR CONTRACTOR LICENSE' TESTS WiTNESBEO BY + P_ATAirtaG� _ SIGNATURES -r;,. :-r•T•a: • ER(.IGNEO) LE ► TB 411MillarAPS Maw r -jib-A! 0.,.�` `�'` ' I' a I - ,r I'1 E G ry /jy� v1� I 'i` r ' T THE IN TION HEAIN I tRUE AND THAT THI R SYSTEM WAS INSTALLED IN Flo- MICE WITH ROW 18-160 AND THE RULES ADOPTED BY THE WA- c ON ADMINIS RATNVE CODE AS ADMINISTERED BY CERTIFICATION 114E STATE FIRE MARSHAL 1. "t P wuA+ .3• .," a i4• - HOLD{PLANT ors TVPq Wm VIILI • +,• - OF CERTIFICATE OF CO JPaTENCY • CEAITIFICATE REGISTRATION N \ • DATE ^(z-p c., Pita-.'11_,--77,7=111 ..mield MI 1500C —